| Item | Parameter Description | Note | |
|---|---|---|---|
| Product Model | LCC02501F | ||
| Cooling Capacity | 12KW | ||
| Primary-side medium | 25% glycol solution | ||
| Secondary-side medium | Max 14L/min | Inverter- adjustable | |
| Primary-side flow | Supply temperature:15~32°C | ||
| Primary-side supply and return water temperature design | Supply and return temperature difference:6~10°C | ||
| Piping Method for Primary and Secondary Sides | Side-inlet/ Outlet Piping | ||
| Cooling Boiling Point | 47+0.5°C | ||
| Pressure | (One Side Supply)4.5bar (Inside Tank)130kPa(Absolute Pressure) |
||
| Liquid Level | 80% of Tank Height | ||
| Cabinet | Product Dimensions(L*W*H mm) | 1800mm*650mm*1870mm | |
| IT Power Supply | AC380V/AC220V/50Hz | ||
| Power Inlet Method | Top Power Inlet | ||
| Others | Operating Weight(kg) | 1680 | |
| Shipping Weight(kg) | 1500 | ||
| Inner Chamber Volume(L) | 80/per unit | ||
| Maximum Noise(dB) | 55dB | ||
| Flame Retardant Rating | Complaint with UL94v-0 | ||
| Environmental Compliance | Complaint with Rohs2.0 | ||
| Insulation Withstand Voltage Rating | >>10MΩ | ||
| Grounding Resistance | <4Ω | ||
| Dehumidification Function | Desiccant Required Inside Tank | ||
| Two- Phase Immersion Liquid | Fluquid LC-50 | ||
Indoor High-Density Liquid-Cooled Cabinet & CDU
Cooling Tower
| Item | Parameter Description | Note | |
|---|---|---|---|
| Product Model | MILC25228FS-0110 | ||
| Cooling Capacity | 25KW | ||
| Secondary-side medium | Electronic chlorinated fluid | ||
| Primary medium | 25% Ethylene glycol solution | ||
| Secondary-side supply and return water temperature design | 37°C~42°C | ||
| Primary-side supply and return water temperature design | 32°C~37°C | ||
| Primary and secondary piping connector method | Side-inlet and outlet piping | ||
| Primary and secondary piping diameter | 1.5inch/ Tri-clamp connection | ||
| Rack | Product dimensions(L*W*H mm) | 1500mm*850mm*1250mm | |
| IT equipment available space(U) | 28 | ||
| IT power supply | AC380V/50Hz/3P | ||
| IT power (kW) | 25 | ||
| Incoming cable method | Bottom cable entry | ||
| Power supply type 1 | PDU | The number of digits in the PDU is ≧13 | |
| Power supply type 2 | Busbar | ||
| Number of IT communication output lines | 28 network cables and 56 fiber optic cables | ||
| Supported number of server units | 1U/2U/4U | ||
| Server dimensions | 21 inches | ||
| Net weight | 530KG | ||
| CDU | Product dimensions(L*W*H mm) | 800mm*850mm*1250mm | |
| Equipment power supply | AC380V/50Hz/3P | ||
| Touch screen interface | 10-inch GUI touchscreen interface | ||
| Incoming cable method | Bottom cable entry | ||
| Equipment power (kW) | 1.5 | ||
| Primary and secondary piping connection method | Side inlet and outlet piping | ||
| Communications protocol | Modbus TCP/ModbusRTU | ||
| Communications interface | RJ45, 48S serial port | ||
| Net weight | 280KG | ||